Download K4000 - USER MANUAL
Transcript
Danaher Motion S.A. CH-1029 Villars-Ste-Croix Dissipation and Dynamic Braking Resistors ratings Model KT4005 KT4010 KT4015 KT4020 KT4030 KT4040 KT4060 KT4090 KT4120 Dissipation Watts 200 400 600 750 900 1200 1800 2700 3600 Braking resistors Ω / Watts - external 22Ω/400W 22Ω/400W 22Ω/400W 15Ω/1200W 15Ω/1200W 6Ω/1500W 6Ω/1500W 4Ω/2000W 4Ω/2000W Type Part Numbering Standalone IP20 units KT40xx-00 KT40xx-01 KT40xx-10 KT40xx-11 Without PC560 and external dynamic braking resistor Without PC560, with external dynamic braking resistor With PC560 and without external dynamic braking resistor With PC560 and with external dynamic braking resistor IP54 cabinet unit KU40xx for cabinet with convection cooling up to KU4015 for cabinet with fan cooling for larger power ratings KV40xx for cabinet with heat exchanger air – air KW40xx for cabinet with heat exchanger air – water KQ40xx for cabinet with air conditioning Overload protection UL requires an external overload protection Connecting the K4000 to a transformer The K4000 can be connected to any input voltage from 3 x 200 V to 3 x 480 V, 50 / 60 Hz, without a line transformer. Nevertheless, if the input voltage is higher than 480 V or the installation requires a galvanic insulation in front of the drive, following rules must be respected: • Don't use an auto-tranformer but only a transformer with separated windings. • The output voltage of the transformer should not be higher than 460 V. Page 8 / 48 User Manual K4000 S476-gb-0348