P0311 – SERIAL INTERFACE BYTE CONFIGURATION
Range:
0 = 8 data bits, no parity, 1 stop bit
1 = 8 data bits, even parity, 1 stop bit
2 = 8 data bits, odd parity, 1 stop bit
3 = 8 data bits, no parity, 2 stop bits
4 = 8 data bits, even parity, 2 stop bits
5 = 8 data bits, odd parity, 2 stop bits
Properties:
CFG
Access groups via HMI:
NET
Default: 0
Description:
It allows programming the number of data bits, parity and stop bits of the serial interface bytes. This
configuration must be identical for all the devices connected to the network.
P0313 – COMMUNICATION ERROR ACTION
Range:
0 = Inactive
1 = Disable via Run/Stop
2 = Disable via General Enable
3 = Change to Local
4 = Change to Local keeping commands and reference
5 = Causes a Fault
Properties:
CFG
Access groups via HMI:
NET
Default: 0
Description:
It allows the selection of the action to be executed by the device, if it is controlled via network and a
communication error is detected.
Table 3.1: P0313 options
Options
0 = Inactive
1 = Disable via Run/Stop
2 = Disable via General Enable
3 = Change to Local
4 = Change to Local keeping
commands and reference
5 = Causes a Fault
Description
No action is taken and the inverter remains in the existing status.
A stop command with deceleration ramp is executed and the
motor stops according to the programmed deceleration ramp.
The inverter is disabled by removing the General Enabling and the
motor coasts to stop.
The inverter commands change to Local.
The inverter commands change to Local, but the status of the
enabling and speed reference commands received via network
are kept, providing that the inverter has been programmed to use
in Local mode the commands via HMI and speed reference via
either HMI.
Instead of an alarm, the communication error causes an inverter
fault, so that an inverter fault reset becomes necessary in order to
restore normal operation.
The following events are considered communication errors:
Serial communication (RS485):
ƒ A128 alarm/F228 fault: Serial communication timeout
The actions described in this parameter are executed by means of the automatic writing of the selected actions
in the respective bits of the interface control words. Therefore, in order that the commands written in this
parameter be effective, it is necessary that the device be programmed to be controlled via the used network
interface. This programming is achieved by means of parameters P0220 to P0228.
CFW700 | 10