Figure 29: Location of Master Module(s)
1
1
FP402 and FP404
2.4.1
2
3
4
FP408, FP412 and FP416.
Potential free relay master modules
Every module consists of 4 relays with a rating of 230 V and 2 A. The master module
allows the assignment of a relay for every detection zone, or for the programming of the
activation of different relays depending on the status of one or different zones (see
chapter 2.4.3).
Figure 30: Location of components on the Relay Master Module
C NO NC C NO NC C NO NC C NO NC
Connection sockets
Connection socket
Trim pot for sounder
delay programming (1 per
relay)
2.4.2
Connection socket
Relay 1 Relay 2 Relay 3 Relay 4
Configuration micro
switch
Master module with 24 VDC outputs (for sounders or other supervised
outputs)
The 24 VDC output master modules have 4 relays that provide 4 additional 24 VDC
outputs. Those outputs can be configured either to power sounders or as 24 VDC
supervised outputs useful for other devices.
These modules have to be powered from an external power source or from the auxiliary
24 VDC output on the main board (for consumption lower than 250 mA). Each module has
Installation, Configuration and User Manual for Conventional Fire Panels FP400 series v2.1