Setting
Description
Range
Default
Quick Check
Specifies whether or not quick check is
performed between standard polling for
class data
Enabled
Disabled
Enabled
Reply Poll Count
The Maximum number of times to poll a
device for Class 2 and 1 data, subsequent to
receiving a positive acknowledgement at the
link layer (CONFIRM:ACK), in response to a
"SEND/CONF user data" request at the link
layer, that was sent due to an application
level request.
0 to 255
10
Max Poll Count
The maximum number of times to poll a
device for Class 1 data before changing to
poll the next device, while performing
background autonomous polling.
1 to 255
3
Reset Link
Function Code
The function code for the reset link request
RESET_CU
RESET_FCB
RESET_FCB
LogicLinx Device
A LogicLinx Device connection is used to define a communications link between the
LogicLinx application running on the D400 and a PC running the LogicLinx Editor.
This connection type can only be created using the LogicLinx Wizard in ConfigPro
CCE. Once assigned, the connection is displayed to provide you with port details.
Modbus Master Stations
The following settings are used when configuring a Modbus Master Station.
Table 18 Modbus Master Station
Setting
Description
Range
Default
Name
Text description to identify the master
station being connected to.
1 to 32 ASCII
characters
MASTERX
Master Station
Address
DNP3 address of the server application
instance.
0 to 65519
X
Map File
Name of the Client map file to be used with
the specific device.
List of user
configured client
map files.
N/A
Application
Parameters
Select the application parameters defining
this connection. The default parameters can
be used, or a custom configuration can be
created. Refer to Modbus Server Application
Settings.
Use Default
Create New…
Use Default
Auto Start Up
Indicates if the client application
automatically starts when the configuration
is changed and reloaded or when the D400
re-boots.
Disabled
Enabled
Disabled