Download D400 Substation Data Manager
Transcript
GE Energy Setting Description Range Default Quick Check Specifies whether or not quick check is performed between standard polling for class data Enabled Disabled Enabled Reply Poll Count The Maximum number of times to poll a device for Class 2 and 1 data, subsequent to receiving a positive acknowledgement at the link layer (CONFIRM:ACK), in response to a "SEND/CONF user data" request at the link layer, that was sent due to an application level request. 0 to 255 10 Max Poll Count The maximum number of times to poll a device for Class 1 data before changing to poll the next device, while performing background autonomous polling. 1 to 255 3 Reset Link Function Code The function code for the reset link request RESET_CU RESET_FCB RESET_FCB LogicLinx Device A LogicLinx Device connection is used to define a communications link between the LogicLinx application running on the D400 and a PC running the LogicLinx Editor. This connection type can only be created using the LogicLinx Wizard in ConfigPro CCE. Once assigned, the connection is displayed to provide you with port details. Modbus Master Stations The following settings are used when configuring a Modbus Master Station. Table 18 Modbus Master Station Setting Description Range Default Name Text description to identify the master station being connected to. 1 to 32 ASCII characters MASTERX Master Station Address DNP3 address of the server application instance. 0 to 65519 X Map File Name of the Client map file to be used with the specific device. List of user configured client map files. N/A Application Parameters Select the application parameters defining this connection. The default parameters can be used, or a custom configuration can be created. Refer to Modbus Server Application Settings. Use Default Create New… Use Default Auto Start Up Indicates if the client application automatically starts when the configuration is changed and reloaded or when the D400 re-boots. Disabled Enabled Disabled D400 Substation Data Manager Software Configuration Guide 41