In a system comprising a single Xtender, the connection of the RCC-02 or RCC-03 units may be
conducted without stopping the Xtender (hot plug).
The communication bus will be used to interconnect other Xtender inverters in the case of a multiunit application or to connect other types of users who have the proprietary protocol of Studer
Innotec. In these cases, the plug-in of interconnected units is done only after the switch-off of the
installation, by disconnecting the battery or by using the main “ON/OFF” button (1) if present.
The 2 switches for the communication bus termination, “Com. Bus" (4) both remain in
position T (terminated) except when both connectors are in use. In this case, and only in this
case, both must be placed in the O open position. If one of the two connectors is not in use,
the two termination switches (14) will be in position T.
5
XTENDER PARAMETER SETTING
All inverters of the Xtender family have many factory settings and some of them can be modified by
the user or installer. Some basic parameters mentioned in Chapter 7 must be set at the
commissioning. For models XTM and XTH, this setting must be done by connecting the remote control
described in RCC-02/03 chap. 7.3.1 - p. 36. For the model XTS four of them can be done directly into
the unit before powering up.
Many features and associated parameters not described in this manual are described further in the
manual accompanying remote control RCC-02/03 or downloaded from the website www.studerinnotec.com.
When the Xtender is connected to the remote control RCC-02/-03 or another Xtender compatible
device (VarioTrack, BSP etc.) it is possible that their software versions differ. It is important to harmonize
the software versions of all Xtender compatible products in a system. The update is made by the
remote control RCC-02/-03 from an SD card with a firmware version at least corresponding to the
most recent device.
5.1
BASIC PARAMETER SETTING IN THE XTS
For XTS models, the 4 parameters / basic functions below can
be modified directly in the compartment inside the door. All
other parameters can be adjusted, if necessary, via the remote
control RCC-02/03.
Before opening the enclosure, it is mandatory to
disconnect all AC and DC sources (battery) of the
product to avoid any risk of electrical shock.
• The battery current charge {1138} as described in chap.
7.3.2 - p. 30 by using the potentiometer (16)
• The max. AC source (input limit) {1107} as described in chap.
7.2.2 - p. 27 by using the potentiometer (18)
• The source current assistance (Smart boost) function {1126} as described in chap. 7.2.2.1 - p. 27 by
using the slide button (19)
• The type of detection of AC-input loss (UPS) Fast/Tolerant/slow {1552} as described in chap. 7.2.1p. 27 by using the slide button (20)
These manual adjustments can be prevented using parameter {1551} on the remote control RCC02/-03. These values will then be defined by parameters from the remote control. If the parameter
{1551} is set to "yes" the buttons 16, 18, 19 and 20 remain inactive even if the remote control RCC-02/03 and/or the communication module Xcom-232i are removed after the initial setting.