Download MAS 711

Transcript
Installation
Base Unit Terminal Description
This table describes the Modbus communication terminals (RS-485) of the base unit:
Terminal number
Type
Description
33
+
Supply to Operator panel, 12 V DC
34
Ground
Supply to Operator panel, ground
35
+
Supply to Pump memory, 12 V DC
36
Ground
Supply to Pump memory, ground
37
Local, A
RS-485, Operator panel, Pump memory and Relay
Module (Modbus master)
38
Local, B
RS-485, Operator panel, Pump memory and Relay
Module (Modbus master)
39
Ext 2, A
RS-485, Power Analyzer (Modbus master)
40
Ext 2, B
RS-485, Power Analyzer (Modbus master)
41
Ext 1, A
RS-485, Central system (Modbus slave)
42
Ext 1, B
RS-485, Central system (Modbus slave)
Pump Memory Terminal Description
This table describes the pump memory terminals:
Terminal number
Type
Description
74
Local, B
RS-485 Modbus slave)
75
Local, A
RS-485 (Modbus slave)
76
Ground
Supply, ground
77
+
Supply, 12 V DC
Operator Panel Terminal Description
This table describes the operator panel terminals:
Terminal number
Type
Description
+
+
Supply, 12 V DC
—
Ground
Supply, ground
A
Local, A
RS-485 (Modbus slave)
B
Local, B
RS-485 Modbus slave)
Power Analyzer Terminal Description
This table describes the Power analyzer terminals:
PAN 311, Terminal number
PAN 312, Terminal
number
Description
11
7
Termination of the last unit in a series of connected units
(T).
12
8
RS-485 (Modbus slave). Receive data + (Rx+, A).
13
9
RS-485 (Modbus slave). Receive data - (Rx–, B).
14
10
RS-485 (Modbus slave), Transmit data + (Tx+, A).
15
11
RS-485 (Modbus slave), Transmit data - (Tx–, B).
Relay Module Terminal Description
This table describes the Relay module terminals:
MAS 711 Installation and Operation