Download Configuration Mode
Transcript
ID50 Series Panel - Installation, Commissioning & Configuration Manual 4.4.1 Loop Wiring Typical connections of analogue addressable loop pair to a loop are shown below. Note: The total length of the communications loop pair cannot exceed 1200 metres using 1.5mm2 cable. The loop wiring MUST be disconnected from the panel during this procedure Checks Before Connection To check the Loop wiring: 1 Link out any isolators on the Loop by temporarily shorting terminals 2 and 4 on each isolator. The following tests should then be carried out using a lowvoltage multimeter. 2 Check the continuity of each leg of the loop and measure the end-to-end resistance. Verify that the total loop resistance (sum of both legs) is less than 40 ohms. Commissioning 3 Connect the meter in normal polarity (+ve to loop +ve and -ve to loop -ve). The meter should initially read low resistance but this should increase as the capacitor in each of the loop devices charges. If the meter indicates the presence of a forward-biased diode then it is probable that one or more of the loop devices is connected in reversed polarity or the wiring is crossed. 4 If reversed device(s) are indicated in step 3, they may be located by successive halving of the loop (if the site layout makes this difficult, the affected section of the loop can be identified from the panel fault messages after the system has been configured and the links in the isolators removed). Note: a. A = Normally open switch - closes under an alarm condition. b. To comply with the requirements of EN54, isolators should be fitted between a maximum of 32 loop devices. For the ID50 Series Panel, do not place more than 25 loop devices between isolators (20 if FET isolators are used). 997-263, Issue 4 September 2002 26