ID50 Series Panel - Installation, Commissioning & Configuration Manual
5.5.8 Pulse On/Off Ratio
The Pulse On/Off Ratio option is used to set the sounder
output pulse ratio to either 1/1 or 4/1. To configure the
ratio:
1
1 From the Commissioning menu, use the numeric keypad
and press the ‘
[Setup] Language =
> : Change
2
or
8
’ button to enter the Setup menu.
English
× : More
< : Exit
2 Press the ‘ 2 / 8 ’ buttons to step through the Setup
menus until the LCD shows the Pulse On/Off Ratio
menu.
[Setup]
> : Change
6
1
Pulse On/Off ratio = 1/1
× : More
< : Exit
Configuration Mode
3 Press the ‘ 6 ’ button to change the required setting
to either 1/1 or 4/1.
[Setup]
> : Change
4 Press ‘
Pulse On/Off ratio = 4/1
× : More
4
< : Exit
’ to return to the Commissioning menu.
5.5.9 Service Phone Number
This option allows a service contact phone number to be
displayed with fault messages. To enter or change the
number:
1
1 From the Commissioning menu, press the ‘ 1 ’ button
on the numeric keypad to enter the Setup menu.
2
or
[Setup] Language =
> : Change
8
< : Exit
2 Press the ‘ 2 / 8 ’ buttons to step through the Setup
menus until the Service Phone Number menu is
displayed.
[Setup]
> : Change
6
English
× : More
Phone = < blank/existing text >
× : More
< : Exit
3 Press the ‘ 6 ’ button to enter the text editing menu.
The existing 20-characters of text are shown on the upper
line. The current cursor position is indicated by a flashing
character. Enter the required telephone number via the
numeric keypad or use the ‘ 2 / 8 ’ buttons to scroll
through the available alphanumeric characters.
[
> : Next
< : Previous
]
× : Char
u1:Delete
3 : Done
u3:Insert
Note: For further information on how to edit text, refer to
Section 5.8, Zone Texts.
4 Press the ‘ 5 ’ button to confirm and return to the
Setup menu.
997-263, Issue 4
September 2002
42