Download User Manual - Z Microsystems
Transcript
Power Considerations The Power Factor gives an indication of what fraction of the apparent power is due to the active power. A purely resistive load (such as a heater or light bulb) has a power factor of 1 (Power Factors can not be greater than 1). Electronic devices (such as switching power supplies) do not draw sinusoidal currents and usually have power factors on the order of (0.6 to 0.8). Example 1 • Power Factor = 1 • A 220V @ 1 Amp resistive heater will have an apparent power of 220VA and an active power of 220W. Example 2 • Power Factor = 0.7 • A switching power supply with a power factor of 0.7 and rated at 120VAC @ 4 Amps will have an apparent power of 480 VA and an active power of 480 * 0.7 = 336 Watts. Most UPS systems are not designed to deliver their full rated power (VA) into purely resistive loads. They are typically designed for power factors as low as 0.6. This means that a UPS rated for 400VA could only supply 240 Watts of active power. Care must be taken that the load does not exceed either of the power ratings, the apparent power rating (VA) or the active power rating (W). Some UPS manufacturers do not give a specification of rated power in Watts. If the rating cannot be obtained, the worse case power factor of 0.6 should be used to calculate wattage rating. Example 3 • A UPS system is rated at 1000VA and no active power is specified. It would be safe to assume that the active power rating is 600 W. UPS Sizing Guidelines When selecting a UPS system for use with the CRD-7220, the power requirements for the shutdown mode must be determined. 1. Determine the number of disk drive enclosures that will be connected to 26