Download Quantum

Transcript
Commissioning
Addressing Modes of the Inputs and Outputs
Overview
In Concept, addresses for each module are assigned individually, therefore this is
not really physical addressing.
Only logical addressing is used in Concept (according to the definition) because the
modules are assigned to the respective registers.
Quasi-physical addressing can be achieved by only using 0x/1x or 3x/4x registers
and assigning them to the bus nodes in increasing order without spaces.
Example
The following diagram provides a clear representation of addressing.
Quantum
CPU
Remote bus
NOA 622
Remote bus branch
Remote bus
Branch interface
16 digital
inputs
16 digital
outputs
Remote bus branch
Branch interface
16 analog
inputs
4 analog
outputs
4 analog
outputs
Addressing
62
Module with ...
Addressing
16 digital inputs
1x1 ... 1x16
16 digital outputs
0x1 ... 0x16
16 analog inputs
3x1 ... 3x16
4 analog outputs
4x1 ... 4x4
4 analog outputs
4x5 ... 4x8
840 USE 497 00 June 2005