1 Power Protection and Conditioning Model Comparison Description VA Ratings Hardwired CVS Hardwired MCR Portable MCR 30 to 7500 VA 120 to 15000 VA 70 to 3000 VA +10/-20% of nominal Input Voltage Range Voltage Regulation ±1% for an input line variation of +10/-20%. No loss of output for line loss of 3 msec. Limits output current to 1.65 x rated current at nominal input. Overload Output Harmonic Distortion 3% total RMS content at full load. 40 dB common and normal code. 120 dB common mode and 60 dB normal mode. Up to 6000 Volt surges are suppressed to a let through of less than 1% per ANSI/IEEE C62.41 Class A & B waveforms. ANSI/IEEE C62.41 Class A & B 6000 waveforms are suppressed to a let-through of less than 0.2%. Noise Isolation Surge Protection ±3% for an input line variation of +10/-20% (50 Hz hardwired units ±5%.) No loss of output for complete line loss of 3 msec. Efficiency Operating Temperature Up to 92% at full load Up to 90% at full load -20oC to 50oC -20oC to 40oC Audible Noise 32 dB to 65 dB 35 dB to 65 dB 34 dB to 49 dB Conformance Listed to UL 1012. CSA Certified UL Listed and CSA Certified. 50 Hz models in compliance with Low Voltage Directive Specification EN60950. Listed to UL 1012. CSA Certified on all models except 3000 VA. 10 years Warranty Note: All values are typical and may vary based on VA ratings of actual units. BTU Output Chart for CVS and MCR Series VA Ratings 120 250 500 750 1000 1500 2000 3000 5000 7500 10000 15000 Total BTU’s 136 225 280 444 519 686 1229 1331 2117 2407 3209 4813 Note: Ratings are for a 40oC ambient temperature. 42 Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solaheviduty.com.