Fitting an earthing switch
key-type interlocking assembly
(contd.)
10 mm
■■ Functions C & T1: position a shim under the probe in order to obtain the 10 mm
dimension.
■■ Function T2: no shim.
■■ Assemble the probe and the earthing switch position indicator with the bolt
supplied (Allen key size 3 + 7 mm open-ended spanner).
■■ Check that the key turns easily, without blocking in the barrel of the lock.
■■ Displace the assembly laterally and in depth to obtain the correct operation.
■■ Tighten the 2 fixing screws.
Preparation of the front plate
■■ Mark the cut-out to be removed from the plate.
AMTNoT153-02