Communicate with an RSView Project over a ControlNet™ Network 14-15 H. Click the Data Collection tab. I. Specify the following parameters: For this item: Do this: Processor Type Select PLC-5. Data Collection Mode 1. Clear the Polled Messages check box. 2. Select the Unsolicited Messages check box. J. Click the Advanced Communication tab. K. Specify the following parameters: For this item: Type or select: Communication Driver driver for the network across which you will send the message Station slot number of the controller that is sending the message Local or Remote Addressing Remote L. In the Remote Routing Configuration dialog box, specify the following parameters: For this parameter: Type or select: Bridge Device 1785-KA5 Bridge/5130-KA Local ID Virtual Link ID from Step D. Local KA5 arbitrary number between 1 and 107 (RSLinx requires an entry but this configuration does not use the entry.) Remote ID number that designates the backplane of the ControlLogix chassis (Use a different number for each backplane.) M. Click OK. N. Click Done and confirm the update of the topic. Publication 1756-UM001E-EN-P - August 2002