Download Logic Panel LP-S044

Transcript
Logic Panel
Input/Output performance
Input performance
Input point
Insulation method
Voltage range
Rated input voltage
Rated input current
Input resistance
Response time
Common method
Output performance
Output point
Insulation method
Voltage range
Rated input voltage
Max. load current
Max. voltage falling when ON
Response time
Common method
16 points
Photo coupler insulation
19.2 to 28.8VDC
24VDC
Approx. 4mA
5.6㏀
1ms
16 points/1COM
(A)
Photo
electric
sensor
16 points
Photo coupler insulation
19.2 to 28.8VDC
24VDC
0.1A/1point, 1A/1COM
Max. 0.2VDC
1ms
16 points/1COM
(B)
Fiber
optic
sensor
(C)
Door/Area
sensor
(D)
Proximity
sensor
(E)
Pressure
sensor
Functional description
Line, rectangle, circle, text, bitmap
Displays the designated device as numerical value.(decimal, hexadecimal, octal, binary, real number)
Displays the designated device value as ASCII character.
Displays current time or date.
Registers alarm history.
Displays generated (not backed up) alarm.
Displays the designated comment as device status or value.
Displays lamp as device status.
Displays the designated parts as device status and value.
Displays several device values with a graph of broken line.
Displays change of device value for time with a graph of broken line.
Displays a device value with a bar graph.
Displays a ratio of several device values with pie graph.
Tags
Figure display
Numeral display
ASCII display
Time display
Alarm history
Alarm list
Comment display
Lamp
Part display
Line graph
Trend graph
Bar graph
Statistic graph
Panel meter
(F)
Rotary
encoder
(G)
Connector/
Socket
(H)
Temp.
controller
(I)
SSR/
Power
controller
(J)
Counter
Displays a device value as panel meter.
Touch key
Numeral input
ASCII input
System information function
Recipe function
Security function
Barcode read function
Floating alarm function
Overlap window
Observe status function
(K)
Timer
Screen is switched, word/bit device values are set when it touched.
Configures user input value in device.
Configures user input ASCII code value in device.
Monitors/Controls LP operation from PLC.
Reads/Writes several PLC device collectively.
Only acceptable user can observe/operate important data.
Connects barcode reader, read barcode.
Warning message is floated when alarm is generated.
Specific bit device is ON/OFF for designated day and time.
Available to form dynamically overlapping another base screen on the base one.
(L)
Panel
meter
(M)
Tacho/
Speed/ Pulse
meter
(N)
Display
unit
(O)
Sensor
controller
Dimensions
(unit: mm)
135
● Panel cut-out
Min. 170
Min. 100
66 - 0
+ 0.5
(Q)
Stepper
motor&
Driver&Controller
136
(R)
Graphic/
Logic
panel
+ 0.5
- 0
(S)
Field
network
device
※Panel thickness
: Max. 4mm
(T)
Software
● Fixing bracket
M4 BOLT
12
(U)
Other
9
65
75
50.5
83
4
145
(P)
Switching
mode power
supply
21.7
R-23