Download Logic Panel LP-S044
Transcript
Logic Panel Input/Output performance Input performance Input point Insulation method Voltage range Rated input voltage Rated input current Input resistance Response time Common method Output performance Output point Insulation method Voltage range Rated input voltage Max. load current Max. voltage falling when ON Response time Common method 16 points Photo coupler insulation 19.2 to 28.8VDC 24VDC Approx. 4mA 5.6㏀ 1ms 16 points/1COM (A) Photo electric sensor 16 points Photo coupler insulation 19.2 to 28.8VDC 24VDC 0.1A/1point, 1A/1COM Max. 0.2VDC 1ms 16 points/1COM (B) Fiber optic sensor (C) Door/Area sensor (D) Proximity sensor (E) Pressure sensor Functional description Line, rectangle, circle, text, bitmap Displays the designated device as numerical value.(decimal, hexadecimal, octal, binary, real number) Displays the designated device value as ASCII character. Displays current time or date. Registers alarm history. Displays generated (not backed up) alarm. Displays the designated comment as device status or value. Displays lamp as device status. Displays the designated parts as device status and value. Displays several device values with a graph of broken line. Displays change of device value for time with a graph of broken line. Displays a device value with a bar graph. Displays a ratio of several device values with pie graph. Tags Figure display Numeral display ASCII display Time display Alarm history Alarm list Comment display Lamp Part display Line graph Trend graph Bar graph Statistic graph Panel meter (F) Rotary encoder (G) Connector/ Socket (H) Temp. controller (I) SSR/ Power controller (J) Counter Displays a device value as panel meter. Touch key Numeral input ASCII input System information function Recipe function Security function Barcode read function Floating alarm function Overlap window Observe status function (K) Timer Screen is switched, word/bit device values are set when it touched. Configures user input value in device. Configures user input ASCII code value in device. Monitors/Controls LP operation from PLC. Reads/Writes several PLC device collectively. Only acceptable user can observe/operate important data. Connects barcode reader, read barcode. Warning message is floated when alarm is generated. Specific bit device is ON/OFF for designated day and time. Available to form dynamically overlapping another base screen on the base one. (L) Panel meter (M) Tacho/ Speed/ Pulse meter (N) Display unit (O) Sensor controller Dimensions (unit: mm) 135 ● Panel cut-out Min. 170 Min. 100 66 - 0 + 0.5 (Q) Stepper motor& Driver&Controller 136 (R) Graphic/ Logic panel + 0.5 - 0 (S) Field network device ※Panel thickness : Max. 4mm (T) Software ● Fixing bracket M4 BOLT 12 (U) Other 9 65 75 50.5 83 4 145 (P) Switching mode power supply 21.7 R-23