Engineering & Facilities Procedure
Number
250.00
Page 3 of 11
E&F Pipe Labeling
Next Review Date:
1-3-2010
Appendix A
Mechanical/Plumbing Piping System Label Sizing
Outside Pipe Diameter Including Minimum Height of Insulation Letters .75” ‐ 2” .75” 2.5” ‐ 6” 1.25” 8” ‐ 10” 2.5” Over 10” Minimum Label Length 8” 12” 24” 3.5” 4" 32” Mechanical/Plumbing Piping System Abbreviations and Letter/Label Coloring
Store Room Sizing Small (S) Medium (M) Large (L) Extra Large (XL) Store Room Sizing Small Pipe Contents Label
Label Colors (Background/Text)
Regulation Laboratory air Air
Blue/White
Carbon Dioxide
Carbon Dioxide
Gray/White
Chilled Water Return
Chilled Water Return
Green/White
Chilled Water Supply
Chilled Water Supply
Green/White
Condensate Return
Condensate
Green/White
ASME A13.1 NFPA 99, JHACO ASME A13.1 ASME A13.1 ASME A13.1 Medium Medium Medium Reverse Osmosis or
Deionized Water
Deionized Water
Green/White
ASME A13.1 Small Green/White
ASME A13.1 Medium Green/White
ASME A13.1 Medium Green/White
ASME A13.1 Medium Small Small Small Domestic Hot Water
Return
Domestic Hot Water
Supply
Domestic Cold
Water
Domestic Hot Water
Return
Domestic Hot Water
Supply
Fuel Oil Return
Fuel Oil Return
Yellow/White
Fuel Oil Supply
Fuel Oil Supply
Yellow/White
ASME A13.1 ASME A13.1 High Pressure Steam
(>15psi)
High Pressure
Steam
Hot Water Heating
Ret.
Hot Water Heating
Sup.
Green/White
ASME A13.1 Medium Green/White
ASME A13.1 Medium Green/White
ASME A13.1 Medium Domestic Cold Water
Standard Labels Label Height 1.125" 2.25" 4" Hot Water Heating Return
Hot Water Heating Supply
Low Pressure Steam
(<15psi)
Low Pressure Steam
Green/White
ASME A13.1 Medium Natural Gas
Natural Gas
Yellow/Black
Sanitary Waste Drain
Sanitary Waste
Green/White
Medium Medium Laboratory Vacuum
Vacuum
White‐black checkerboard / black boxed ASME A13.1 ASME A13.1 NFPA 99, JHACO Small