TRAINING MANUAL ECO3™ INSTALLATION ADDITIONAL EQUIPMENT A certified 24VAC power supply (not supplied) is required for the unit. It is recommended to put an in-line fuse (250V/1A) from the power supply to the ECO³™ (see wiring diagrams). It is also recommended to place an in-line fuse (250V/5A) onto each of the incoming controls voltages to protect the ECO3™ from power surges that might harm its internal circuitry (see wiring diagrams). Damage due to power surges is not covered by the manufacturer warranty. INSTALLATION Safety Warning ! 3 Installation and maintenance of the ECO ™ must be carried out at 3™ all times by suitably qualified persons. The ECO must be installed in strict compliance with the national wiring rules. 3 The 24 VAC power supply to the ECO ™ must be protected by a suitable switch fuse or circuit breaker. The back plate of the ECO3™ is attached to a flat surface via four screws. The unit is then inserted onto the back plate and pushed up until it clicks into place. If theft is not a concern, the locking mechanism can be bent to make it easier to remove once installed or the backplate can be installed upside down. The unit may then be wired into the system via the cable housing on the bottom of the ECO3™ (see wiring instructions later in this manual). ©Copyright 1986 – 2006 Page 3 of 18 Smartcool Systems Inc. All Rights Reserved