Denomination
[Y] LED
AUTOMATIC
BYPASS
[Z] LED
ON Blinking:
Note
Indicates disablement of
automatic extinguish
commands, via key [G]
(refer to the previous table
5.1.1 Commands).
Indicates disablement of
manual extinguish
commands, via key [H]
(refer to the previous table
5.1.1 Commands).
MANUAL
BYPASS
[A1] LED
EXTINGUISH
[B1] LED
PREEXTINGUISH
[C1] LED
FAULT
[D1] LED
STOP
EXTINGUISH
[E1] LED
CPU FAULT
5.2
ON Solid:
Indicates that fire
extinction is running.
Indicates activation of the
pre-extinguish output,
refer to “Connecting the
Extinguishant module
(optional system
enhancement tool)” on
page 30, terminal J4.
Indicates that only
one zone is in alarm
status, therefore,
the extinguishant
system will not be
activated. If another
zone latches in
alarm, the
extinguishant
system will be
activated.
Indicates trouble with the
fire extinction circuits.
Indicates restoral of
a fault event.
Indicates that the fire
extinguishant system has
been stopped from a
remote Hold-off unit (refer
to “Connecting the
Extinguishant module
(optional system
enhancement tool)” on
page 30, terminal J7).
Indicates restoral of
a Stop extinguishant
event.
Indicates a CPU fault that
requires immediate repair.
Indicates restoral of
a fault event.
This condition can be cleared by reset only
(level 2).
Internal LEDs
A
B
C
Figure 7 - Internal LEDs
These LEDs indicate communication between the panel and the detectors. These LEDs indicate that
the panel is interrogating its devices, the protocol it is using and whether or not the interrogated
devices have responded.
The green LED [A] (nearest to the Loop-I terminals) will blink each time a loop device responds during
the interrogation phase of the devices from address 1 through to the maximum number of devices
allowed (refer to Appendix B and Appendix C regarding the number of devices accommodated by the
loop).
User Interface