Download GUARDPOINT LITE

Transcript
Notes:
1- To make the GUARDPOINT LITE Program send automatically the commands to the modem near the
PC, record these commands in a ‘Modem.txt’ file. Leave the last line of the file empty.
2- If the calling modem near the PC is used also for other applications (Internet, etc…); this Programming
may prevent these applications to work properly. To set back the modem as it was before, do as follows:
- Either send command ATZ to the modem (through the HyperTerminal Programme for example)
- Or, if it is an external modem, power it off and then on.
- Or, it is an internal modem, shut down the PC and switch it off and then on again.
4- Modem Connection:
The serial connector (D25 or D9) of the Remote station modem serial port must be connected as follows:
- Rx signal (pin 2 if D25 or 3 if D9) to signal Tx of the controller or the RS232/RS485 interface.
- Tx signal (pin 3 if D25 or 2 if D9) to signal Rx of the controller or the RS232/RS485 interface.
- DTR signal (pin 20 if D25 or pin 4 if D9) must be always high (between 7 & 12 volts): connect it to the
+V pin of the RS232/RS485 interface or to 12vDC of a controller if the modem is connected directly to this
controller.
- D25 pins 4 and 5 (or 7 & 8 if the D9 connector) shorted together.
Multi controllers Station
MODEM
Dtr Rx Tx 0v
(7v to 12v)
RS232
If D9: 4 3 2 5
If D25: 20 2 3 7
Controllers are connected, thorugh their
RS485 port, to a RS485/232 interface
which is connected to the modem.
+ short 7&8
+ short 4&5
Telephone Line
COM i
MODEM
+V Tx Rx 0v
RS232 / RS485 H
L
Interface
Hi CNT1
Lo
RS485
Hi
Lo
CNT2
CNTn
Telephone Line
One controller Station
Fig. 2.1: Example of stations
Architecture
The controller is connected directly
to the modem through its RS232
port.
MODEM
Dtr Rx Tx 0v
(7v to 12v)
RS232
If D9: 4 3 2 5
If D25: 20 2 3 7
+ short 7&8
+ short 4&5
+12V Tx Rx 0v
CNT1