Download TECOMAT FOXTROT PROGRAMMABLE CONTROLLERS
Transcript
TECOMAT FOXTROT programmable controllers DOWN - impulse input for counter decrementation CLK - impulse input for counter DIR - counter direction CLR - counter reset CAP - capturing of the counter value V - first track IRC G - second track IRC NI - clearing pulse IRC MD - measuring contact As can be seen in the table 3.1.5, both counter objects can be adjusted to different mode combinations providing that the first object uses only inputs DI0 and DI1 (first 5 modes). If the first object uses all DI0 to DI3 inputs, then the second object is switched off. According to the configuration we can have available up to 4 simple one-way counters or 2 simple two-way counters / IRC or 1 counter / IRC including reset and capturing. Modes of impulse length measuring and period and phase shift measuring are designated for periodic signals only. These measurements are loaded by a live error arising due to occupance of the periphery processor during the data transmission with the central unit. This error is eliminated so, that the resultant value of the measuring is gained as an average of the last eight pulses captured. Thus, it is supposed that the detected signal is presented by impulses repeated with a certain periodicity. An absolute error of the measurement is max. ± 10 µs and decrease in connection to the PLC cycle time extension. The meanings of each function are described in the chapter 2.3.6. Counter inputs are connected similarly to standard inputs as shown in the fig.3.1.2. In fig.3.1.3 and fig.3.1.4 you can see examples of the IRC position sensors connection. IRC1 + – V IRC2 G + – V G + =24V U – Fig.3.1.3 Example of two IRC incremental encoders connection 95 TXV 004 10.02