Counter Type
This parameter specifies the counter configuration type. A4 selects four identical,
independent (Type A) counters. B1-3, A4 selects one Type B counter (for A-Quad-B
counting) and one Type A counter.
Output Failure Mode
If the module detects a loss of the CPU, it can respond in three different ways:
D
it can continue to operate normally, processing the inputs and controlling the
outputs according to its configuration (NORMAL);
D
D
it can force all four outputs to turn off (FRCOFF);
the module can hold the outputs at the current state (HOLD).
These responses remain in effect until the CPU returns to operation or the module is
power-cycled.
Counter Direction
Each counter can be configured to count either up or down. The default is Up.
Counter Mode
Each counter on a module has programmable count limits that define its range. The
counter can either count continuously within these limits, or count to either limit, then
stop.
Continuous Counting
In the continuous counting mode, if either the upper or lower limit is exceeded, the
counter wraps around to the other limit and continues counting. Continuous counting is
the default mode.
Single-Shot Counting
If single-shot counting is selected, the counter will count to its upper or lower limit, then
stop. When the counter is at the limit, counts in the opposite direction will count it back
off the limit. The Accumulator can also be changed by loading a new value from the CPU
or by applying a Preset Input.
Note
In either the single-shot or continuous mode, the counter stops at 1 past
the limit (that is, at n+1 if n is the high limit, and n–1 if n if the low
limit). Therefore, where N is the desired number of pulses to be
counted, you must configure the counter so that high limit=N–1, or
low limit=N+1.
GFK-0402G
Chapter 4 Series 90 Micro PLC Configuration
4-11