WLDR ReferenceBook Page 143 Thursday, April 5, 2001 3:36 PM
WindLDR™ Reference Manual
9-143
Finally, optionally enter any associated comment in the Tag Name
Comment: field. This reference may be a maximum of six characters
per line for a maximum of four lines.
Once the dialog box is complete, click the OK button to activate the
digital read instruction on your ladder. To back out of this instruction
without utilizing the digital read instruction, click the Cancel button.
To access on-line help, click the Help button.
NOTE:
The right mouse button is context-sensitive to the specific PLC selected. This
chapter is written in reference to the Micro3 PLC. To access the right mouse button instructions for another PLC, select the Configure ➔ PLC Selection option.
DGRD
BCD4
I
*****
Q
****
Conversion:
BCD or BIN
Quantity of Digits 1st Input #:
0 –32
1 –5
D1
****
1st Output #:
0 –31
When an input is on, the data designated by I and Q is set to 16 internal relays
or data registers designated by destination operand D1.
This instruction can be used to set preset values for timer (TIM, TMH, and TMS),
counter (CNT), and counter comparison instructions using digital switches.
NOTE:
The DGRD instruction can be used on transistor output type Micro3 base
units only. The DGRD instruction can be used only once in a user program.
NOTE:
Do not use the DGRD instruction between JMP and JEND instructions or
between MCS and MCR instructions.
© 2001 IDEC Corporation
9. Editing the Ladder