This Fire Control panel can only be programmed using
the Software FireClass Console release 1.0 or higher.
Control panel FW ver. 1.0 or higher.
TYCO and BENTEL SECURITYsrl shall not assume
the responsibility for damage arising from improper application or use.
Installation of this Control panel must be carried out
strictly in accordance with the instructions described in
this manual and in compliance with the local laws and
bylaws in force.
The FC501 Fire Control panels comply with the essential requirements of standards EN54-2; EN54-4 and
EN54-21.
Contents of the box and Unpacking
The control panel is contained in a carton box, inside
which are located:
Ø the plastic cabinet (backplate and cover) with the
motherboard and the power supply Switching assembled.
Ø The Quick Start Guide.
Ø A transparent plastic bag inside:
- A CD-ROM with Installation and User manuals and
the FireClass software console to manage the panel;
- Another transparent plastic bag containing:
-the KST thermal Probe;
- Two 3.9 kOhm resistors;
- a red and a black cable L = 300 mm with a faston
terminal to connect batteries;
- a black cable L = 300 mm with two faston terminal to
connect batteries. Proceed carefully to unpack the
contents and dispose of recyclable materials in accordance with the local law.
Recycling information
The manufacturer recommends that customers dispose of their used
equipment (panels, detectors, sirens, and other devices) in an environmen-
0051
BENTEL SECURITY s.r.l.
Via Gabbiano, 22 - Zona Ind. S. Scolastica
64013 Corropoli (TE) - ITALY
13
0051-CPD-0406 (FC501-L)
0051-CPD-0407 (FC501-H)
EN 54-2:1997+A1:2006 EN 54-21
Control and indicating equipment for fire detection and fire alarm
systems for buildings with alarm transmission and fault warning
routing equipment.
EXPECTED OPTIONS
Fault signals from points
Dependencies on more than one alarm signal: type A and B
Delays to outputs
Disablement of addressable point
Test condition
Output to fire alarm device
EN 54-2 ESSENTIAL CHARACTERISTICS
Performance under fire conditions
Passed
Response delay (response time to fire)
Passed
Operational reliability
Passed
Durability of operational reliability, Temperature resistance Passed
Durability of operational reliability, Vibration resistance
Passed
Durability of operational reliability, Electrical stability
Passed
Durability of operational reliability, humidity resistance
Passed
EN 54-21 ESSENTIAL CHARACTERISTICS
Performance of transmission
Passed
Operational reliability
Passed
Durability of operational reliability, Temperature resistance Passed
Durability of operational reliability, Vibration resistance
Passed
Durability of operational reliability, Electrical stability
Passed
Durability of operational reliability, humidity resistance
Passed
EN 54-4 ESSENTIAL CHARACTERISTICS
Performance of power supply
Passed
Operational reliability
Passed
Durability of operational reliability, Temperature resistance Passed
Durability of operational reliability, Vibration resistance
Passed
Durability of operational reliability, Electrical stability
Passed
Durability of operational reliability, humidity resistance
Passed
tally sound manner. Potential methods include reuse of parts or whole products and recycling of products, components, and/or materials.
Waste Electrical and Electronic Equipment (WEEE)
Directive
In the European Union, this label indicates that this product
should NOT be disposed of with household waste. It should be deposited at an appropriate facility to enable recovery and recycling.
NOTE- The FC501 Fire control panel can support several addressable devices (Detectors, Modules, Manual call Points, etc). The present manual includes the instructions for their programming, but for
further information on those devices and their accessories, please visit: www.fireclass.net, logging in the Reserved Area, under Installation Manuals.
The manufacturer reserves the right to change the technical specifications of these products without prior notice.
0051
BENTEL SECURITY s.r.l.
Via Gabbiano, 22 - Zona Ind. S. Scolastica
64013 Corropoli (TE) - ITALY
13
0051-CPD-0408 (FC500IP in FC501-L/FC501-H)
EN 54-21
Alarm transmission and fault warning routing equipment for fire
alarm systems installed in buildings.
EN 54-21 ESSENTIAL CHARACTERISTICS
Performance of transmission
Passed
Operational reliability
Passed
Durability of operational reliability, Temperature resistance Passed
Durability of operational reliability, Vibration resistance
Passed
Durability of operational reliability, Electrical stability
Passed
Durability of operational reliability, humidity resistance
Passed