Download 3 - Schneider Electric

Transcript
Logic discrimination
Principle
Control and monitoring
functions
Operation with GOOSE messages and logic inputs (Gx)
Equipped with the ACE850 interface, Sepam series 80 can be used for logic
discrimination with GOOSE logic inputs and the IEC 61850 protocol on Ethernet
TCP/IP.
The first logic group is active if one of the following two conditions is fulfilled:
b blocking reception 1 is assigned to a GOOSE logic input (G401 by default), except
for Sepams used in motor applications where this input does not exist
b blocking send 1 is created by sending a GOOSE logic discrimination blocking
message over the Ethernet network.
The second logic group, when present in the application, is active if one of the
following two conditions is fulfilled:
b blocking reception 2 is assigned to a GOOSE logic input (G402 by default)
b blocking send 2 is created by sending a GOOSE logic discrimination blocking
message over the Ethernet network.
DE80560
Level "n+1" Sepam
Reception
BSIG1 BSIG2
ACE850
4
Ethernet TCP/IP
Send BSIG1 output
ACE850
to other level "n" Sepam
BSIG1 BSIG2
Send
Send BSIG2 output
to other level "n" Sepam
Level "n" Sepam
Logic discrimination using the IEC 61850 protocol and GOOSE logic inputs (Gx)
SEPED303001EN - 01/2013
259