Download POWER ELECTRONICS
Transcript
G9.5 COMPARATOR 1 OFF DELAY Screen Description Range Unit Default Value Function 5 T COMP1 OFF=5s Comparator 1 OFF delay. 0 to 99 Seconds. 5 Set the OFF delay condition for the comparator. EXAMPLE: When motor current exceeds rated current a relay could be used to warn against motor overload. G9.1 COMPR1 SEL = 1 G9.2 COMP1 ON = 100% G9.3 COMP1 OFF = 80% G9.4 T COMP1 ON = 10s G9.5 T COMP1 OFF = 10s G7.1 REL1 SEL= 6 % I motor Motor current 100% 80% 0% Relay Status T >10s T >10s Time ON OFF DT0037B Figure 41. Comparator relay configuration. G9.6 COMPARATOR 2 SOURCE SELECTION Screen Description Range 6 COMPR2 SEL=1 Comparator 2 source selection. 0 to 8 (See table 11 in G9.6) G9.7 COMPARATOR 2 ON SETPOINT Screen Description Range Unit Default Value Function 2 COMP2 ON=100% Comparator 2 ON set point. 0 to 500% % of function selected (G9.6). 100% Set the comparator ON set point. If the value of the source selected is higher than the ON set point for the time specified at G9.4, the output state of this comparator changes to ON. One of these relays must be selected as a comparator, see screens group G7. G9.8 COMPARATOR 2 OFF SETPOINT Screen Description Range Units Default Value Function 68 8 COMP2 OFF=80% Comparator 2 OFF set point. 0 to 500 %, % of function selected (G9.6). 80. Set the comparator OFF set point. If the value of the source selected is lower than this OFF set point for the time specified at G9.10 the output of this comparator changes to OFF. One of these relays must be selected as a comparator, see screen group G7. POWER ELECTRONICS Technical Manual V5 MT0001 Rev. F