Download Select POINT I/O Modules

Transcript
3
1734 POINT I/O modules offer 1 to 8 points per module. The I/O modules are
interfaced to a network through a communication interface, which includes a built-in
power supply that converts incoming 24V dc power to 5V dc backplane power. Each
type of communication interface supports a maximum of 13 to 17 I/O modules, with
a maximum of 10 A field power. The I/O modules receive power from the power
supply through the backplane. You can expand a POINT I/O assembly up to a
maximum of 63 I/O modules or 504 channels.
1734D Series POINTBlock I/O provides a DeviceNet communication interface with up
to 16 integrated I/O points in a single module. You can add up to 13 POINT I/O
modules to a POINTBlock I/O assembly, for a maximum of 120 channels per
assembly.
POINT I/O Features
y Highly modular design (1 to 8 point modularity)
y Broad application coverage
y Channel-level diagnostics (LED indicator and electronic)
y Channel-level alarm and annunciation (electronic)
y Parameter-level explicit messaging
y Removal and insertion under power (RIUP)
y Network solutions with multiple DeviceNet interfaces, ControlNet, EtherNet/IP, and
PROFIBUS DP adapters
y Channel-level open-wire detection with electronic feedback
y Vertical mounting without derating
y 5 g vibration
y Channel-level short-circuit detection with electronic feedback
y Flash upgradable adapters
y Electronic and mechanical keying
y Robust backplane design
y Hot swapping of I/O modules
y Built-in DIN-rail grounding
y Mounting base provides continuous backplane and field bus power
y Color-coded module labels
y UL, C-UL, CE, C-Tick, DeviceNet, EEx certifications (as marked)
y Highly reliable structural integrity
y Optical isolation between field and system circuits
Publication 1734-SG001C-EN-P — May 2006