Technical data LHX 20
(only air/water heat exchanger)
Cooling performance *)
Heat exchanger
Dimensions LHX 20
&RROLQJSHUIRUPDQFH
Cooling performance
Cooling performance measured with
cool water intake temperature of
15 °C and water circulation volume of
1.55 m3/h, air expulsion
temperature 25 °C
Adjustment range air expulsion
temperature
Max. deviation
Water pre-circulation temperature
Air expulsion temperature *)
:DWHUFLUFXODWLRQ
Cooling medium1)
Water intake temperature2)
Water circulation volume
Pressure loss in the equipment
at 1.55 m3/h
Water pipe
Water connection intake/exit
Condensation connection
$LUFLUFXODWLRQ
Air flow regulated, dependent on
temperature
Water pre-circulation temperature
1) at 2.8 m3/h water
2) at 1.55 m3/h water
*)at constant air intake temperature of 40 °C
01005093 01005094
up to 20 KW
12 KW
18 ... 30 °C (in 0.1 °C increments)
앐2K
Water
6 ... 15 °C
up to 2.8 m3/h
0.5 bar
Copper
Rp 1"
Rp 1/2"
1000 .... 3000 m3/h
(OHFWULFDOGDWD$&
Supply voltage (single phase)
Max. current intake
Max. power intake
Apparent output at full capacity
Back-up fuse
230 VAC (50/60 Hz)
4.3 A
700 W
990 VA
10 A
(OHFWULFDOGDWD'&
Supply voltage
Max. current intake
Max. power intake
Back-up fuse
48 VDC
13 A
624 W
16 A
,QWHUIDFH
ST-Bus (RJ 45)
RS 232 (SUB-D 9 pole)
Digital input/output signals
(SUB-D 25 pole)
Connection possible for external
use and digital display
ASCII protocol, status indication:
temperature, humidity level, fan
operation times, target values
External input/output, alarm output
and warning
*HQHUDOGDWD
Type of protection
IP 20
Ambient temperature during transport –25 ... 70 °C
Relative humidity
5 ... 95 %
Weight
78.5 kg (82 kg with water)
1) For trouble-free operation of the air/water heat exchanger the water
conditions have to be adhered to (VDE 3803, please also see
User Manual)
2) With water intake temperatures of < 6 °C and > 15 °C a precise control
cannot be achieved