Power Cable Connection
RELAY Connection
■ Use Vinyl insulation wire 0.9~2.0㎟ (Allowed Rating Voltage
300V max) or higher leveled cable for power cable connection.
N
L
!
CAUTION
RLY_NO
Be sure to keep L(Hot) and N(neutral) status connection.
Otherwise, it may result for operation default and defect.
B
+
mV,V
INPUT
-
■ Recommended CR FILTER
▶ Seong Hoo Electronics
▶ HANA PARTS CO.
▶ Songmi Eolectic Co.,Ltd
▶ Jiwol Electric Co.,Ltd
▶ Shinyoug Communications Co.,Ltd
NOVA300
NOVA300
Class 3 Ground
Class 3 Ground
3. DC CURRENT INPUT
RTX+
RTX-
RTX-
RTX-
Terminating
Resistor
Class 3 Ground
Class 3 Ground
: BSE104R120 25V (0.1μ+120Ω)
: HN2EAC
: CR UNIT 953, 955 etc
: SKV, SKVB etc
: CR-CFS, CR-U etc
To prevent electric shock, be sure to turn off the NOVA300 controller
and source circuit breaker before wiring.
!
CAUTION
1. In case of DC RELAY
External DC
Power
Master
INPUT
Vinyl insulated wire 0.9~2.0㎟ (Allowed Rating Voltage 300V max)
Class 3 Ground
ANALOG OUTPUT Connection
1. SSR / SCR
CAUTION
4∼20mADC,
600Ω max
SHIELD
+
Actuator
!
2. RET
!
SHIELD
Receiver
(Recorder
etc)
OUT1NOVA300
Class 3 Ground
SCR : 4∼20mADC, 600Ω max
SSR : 12VDC min, 600Ω min
+
RET+
-
RETNOVA300
!
CAUTION
Display Error and Correction
R
Class 3 Ground
To prevent electric shock, be sure to
turn off the NOVA300 controller and
the source circuit breaker before
connection/disconnection of the
actuator as well as wiring.
CAUTION
External AC
Power
Master
To prevent electric shock, be sure to
turn off the Nova controller and the
source circuit breaker before
connection/disconnection of the
receiver as well as wiring.
!
CAUTION
!
CAUTION
Never touch the terminal in the rear panel to prevent electric shock when
power is supplied to the controller, and Be sure to turn off the electric
power before wiring.
Bind the wires connected to the controller terminals neatly together in
order to prevent electromagnetic wave radiation.
!
RELAY
(Rating Specification of RELAY COIL should be used lower than the Contact
Rating of Controller)
2. In case of AC RELAY
OUT1+
-
Use M3.5 screw-compatible crimp-on terminals with insulating
sleeve as shown below.
DIODE
(Need to connect direct to RELAY COIL Terminal
CAUTION (SOCKET))
R
To prevent electric shock, be
sure to turn off the NOVA300
!
CAUTION Controller and the source
circuit breaker before wiring.
Φ3.0㎜ or over
Terminal Specification
NOVA300
!
RTX+
Power Cable Specification
+
R
-
CAUTION
RTX+
■ Up to 31 slave controllers(NOVA300 series instruments equipped with communication
option) can be multidrop-connected.
■ Be sure to connect terminating resistors(220Ω, 1/4W) to slave and master controllers
at communication-channel ends as shown above.
SHIELD
DCmA
NOVA300
Controller
SHIELD
■ When using an auxiliary relay or inductance load (L) such as solenoid, be sure to insert
a CR filter(for AC) or diode (for DC) in parallel as a surge-suppressor circuit to reject
sparks, preventing malfunction or damage.
SHIELD
INPUT
NOVA300
Controller
Terminating
Resistor
Use an Auxiliary RELAY
2. DC VOLTAGE INPUT
A
RTD
CAUTION
Master Station
To protect electric shock, be sure to turn
off the NOVA300 controller and the
source circuit breaker before wiring.
NOVA300
SHIELD
b
!
COM
ANALOG INPUT Connection
1. RTD INPUT
Communication Wiring (RS485)
CR FILTER
(Need to connect direct to RELAY COIL Terminal
(SOCKET))
Display ERROR
ERROR Contents
Correction
E.SYS
EEPROM, DATA Loss
Ask repair
E.RJC
RJC SENSOR Failure
Ask repair
Communication Failure
Comm Cable
CHECK
S.OPN
SENSOR Open
SENSOR CHECK
E.AT
AT Time Out (27h over)
PROCESS
CHECK
Flash Decimal
point of SP
RELAY
(Rating Specification of RELAY COIL should be used lower than the Contact
Rating of Controller)
Terminal Arrangement and External wiring
SD390
SD360
ALARM
RS485
ALARM
11
ALM 1
12
ALM 2
13
COM
RET
ALARM
RTX+ 21
+ 21
21
ALM 3
RTX- 22
- 22
22
COM
11
ALM 1
N
12
ALM 2
L
13
COM
POWER
14
15
MAX:19.2kbps 4-20mA DC RELAY Contact Rating:
250V AC 1A/30V DC 1A
RELAY Contact Rating:
250V AC 1A/30V DC 1A
100-240V AC
50/60Hz
TC INPUT mV/V INPUT RTD INPUT
RELAY Contact Rating:
250V AC 1A/30V DC 1A
POWER
14
15
21
11
N
1
12
22
2
13
23
3
14
24
2
+
2
+
3
-
3
-
1
A
2
b
3
B
15
15
14
13
3
RS485
RET
12
11
22
21
RTX+ 21
+ 21
2
1
RTX- 22
- 22
L
MAX:19.2kbps 4-20mA DC
100-240V AC
50/60Hz
ALARM
23
ALM 3
ALM 4
24
COM
TC INPUT mV/V INPUT RTD INPUT
RELAY Contact Rating:
250V AC 1A/30V DC 1A
Dimension and Panel Cutout
2
+
2
+
3
-
3
-
1
A
2
b
3
B
How to install Mount
SD390
SD390
SD360
A
C
SD360
E +0.6
0
Panel Thickness
( 1mm~10mm )
MODEL
A
B
C
D
E
F
G
H
I
SD390
96
96
120
120
92
92
96
4
92
SD360
96
48
120
70
92
45
-
-
-
G*N-H +70
N:the Number of unit
1) Cut the mounting panel. (Refer to Dimension and Panel Cutout)
2) Insert the controller into the panel cutout with the rear terminal board facing ahead.
3) Attach the right and left mount and fix it to the panel.(Use driver)