GVS K-BUS○R KNX/EIB Temperature Control Panel Bit3: flag of enabling frost / heat protection mode 1---enable Bit4: flag of banning temperature control 1---banned 0----disable 0----enabled Bit5: flag of heating/cooling 0—cooling,1—heating. Bit6: flag of dead zone Select both heating and cooling control functions, and when the current temperature is in the dead zone, set 1, otherwise set 0. Bit7: flag of frost alarm When the actual temperature is below 5 ℃, set 1, otherwise set 0. This bit is only as alert signs, has no effect on the temperature control. 18 Output RHCC status RHCC Status Report Temperature control 2 byte C, R, T 1bit/byte C, R, T Bit no: 0: error, “1” alarm,“0” normal 8: heating or cooling, "0" cooling, "1" heating 12: Dewpoint alarm, "1" alarm, "0": normal 13: frost alarm, "1" alarm, "0": normal 14: 19/20/24/25 over-heat/cold alarm "1" alarm, "0": normal Basic/ heating/cooling control value Temperature control Additional heating/cooling control value This communication object is used to send the control value of heating /cooling, to control actuator ON/OFF, and adjust the room temperature. Send telegrams(two position control――1bit):on/off Send telegrams(two position control ――1byte) :0%/100% Send telegrams(continuous PI control) :0…100% Send telegrams(switching PI control) :on/off Send telegrams(switching PI control) :on/off Send telegrams(fan coil control):0…100% 21 fan automatic or fan manual Fan 1 bit C, R, T This communication object is used to switch over fan between auto and manual. when parameter "Switchover fan between auto and manual" selects "object 'Automatic ON/OFF'", Send the telegram "1" - fan automatic Send the telegram "0" - fan manual when parameter "Switchover fan between auto and manual" selects "object 'Manual ON/OFF'", 74 www.video-star.com.cn maketing@video-star.com.cn Tel.:(8620)39338986 Fax.:(8620)39338465