Working Draft- All Hazard Receipt Facility Protocol
Guidance
Figure 1. Summary of AHRF Screening Protocols
SAMPLE RECEIPT and TRANSPORT CONTAINER SCREEN: Outside AHRF
Establish/Continue COC
Review corresponding documentation and Interview the delivery technician
Visual inspect transport container (check for explosive device, radiation and unusual liquid
or powder. If present collect sample, mitigate hazard and contact appropriate authorities)
Document observations, complete Sample Receipt Forms, and assign tracking identification
Carry out a Threat Assessment and develop a Screening Plan
PRIMARY SAMPLE CONTAINER SCREEN : Inside fume hood
Screen headspace of transport container for CWAs with IMS and FSP
Remove contents from transport container and secondary containment (if necessary)
Visually inspect and screen primary sample container for radioactivity (surface screen),
explosives (colorimetric), and CWA (colorimetric)
If hazards are indicated, collect exterior wipe sample, mitigate hazards indicated via
decontamination of exterior surface or shielding, and contact appropriate authorities
Document observations and results on AHRF Screening Results Form
Assess need to continue screening process and ability to transfer to glove box
PRIMARY SAMPLE SCREEN: Inside glove box and biosafety cabinet
Transfer primary sample container to glove box
Open primary container and screen for VOCs (PID) and combustible gases (CGI)
Screen primary sample for radiation (surface scan)
If sufficient amount of sample is present, split sample and continue screening process
Remove small portion of the sample and transfer into the biosafety cabinet. Conduct the
optional screen using IMS and/or FSP. Conduct the thermal susceptibility test to determine
if explosive materials are present.
Perform water solubility and reactivity test
Perform DB-3 Dye test for alkylating agents (colorimetric)
Perform pH and starch iodide test (colorimetric)
Perform nerve agent test (colorimetric)
Perform the additional chemical screening as needed (colorimetric)
Document observations and results on AHRF Screening Results Form
DOCUMENT RESULTS
Complete and verify AHRF Screening Results Forms
Compile all forms into a single AHRF Screening Report
Contact sampling agency, appropriate local authorities, the local laboratory director, and the
FBI WMD Coordinator
Prepare sub sample and primary sample for delivery to the designated laboratory(ies) and/or
sampling authority
Transfer to the bio safety cabinet to await transfer
Acronyms:
CGI- Combustible Gas Indicator CWA- Chemical Warfare Agent FSP- Flame Spectrophotometer
IMS- Ion Mobility Spectrometer PID- Photoionization Detector WMD- Weapons of Mass Destruction
VOC- Volatile Organic Compounds COC- Chain of Custody
25 September 2006