Download PM810 Ref.book
Transcript
PowerLogic® Series 800 Power Meter Chapter 6—Alarms 63230-500-201A3 6/2006 Table 6–2: Scale Groups Scale Group Measurement Range Scale Factor Amperes Scale Group A—Phase Current 0–327.67 A –2 0–3,276.7 A –1 0–32,767 A 0 (default) 0–327.67 kA 1 Amperes Scale Group B—Neutral Current 0–327.67 A –2 0–3,276.7 A –1 0–32,767 A 0 (default) 0–327.67 kA 1 Voltage Scale Group D—Voltage 0–3,276.7 V –1 0–32,767 V 0 (default) 0–327.67 kV 1 0–3,276.7 kV 2 Power Scale Group F—Power kW, kVAR, kVA 82 0–32.767 kW, kVAR, kVA –3 0–327.67 kW, kVAR, kVA –2 0–3,276.7 kW, kVAR, kVA –1 0–32,767 kW, kVAR, kVA 0 (default) 0–327.67 MW, MVAR, MVA 1 0–3,276.7 MW, MVAR, MVA 2 0–32,767 MW, MVAR, MVA 3 © 2006 Schneider Electric. All Rights Reserved.