7 APPLICATION FUNCTIONS MELSEC-Q The network module issues a system switching request when the status of data link is changed from "under data link" to "data link halted." (when the D.LINK LED of the network module turns off.) Although the time interval from when the data link is stopped to when the system switching request is issued to the QnPRHCPU is set to two seconds, the interval can be changed using the link special relay SB and link special register SW. To issue the system switching request immediately after detecting that data link is stopped, reduce the system switching monitoring time. However, note that a system switching request is issued frequently if the network is not stable and the system switching monitoring time is reduced too much. Link special relay and link special register used for setting a system switching monitoring time Number Name Description SB0018 Switching monitoring time setting enable flag Indicates whether the switching monitoring time setting is enabled or disabled. OFF : The switching monitoring time setting (SW0018) is disabled. ON : The switching monitoring time setting (SW0018) is enabled. SW0018 Switching monitoring time setting Set a time from the detection of a data link halt to issue of system switching request in the redundant system. 0: 2s (default) 1 to 500: in 10ms (set up in 10ms units within the range of 10ms to 5s.) To reduce the system switching time from 2s to 0.5s, set SB0018/SW0018 in the sequence program as follows. System switching monitoring time setting enable directive Set up a system switching time of 0.5s. Enable the SW0018 setting. System switching monitoring time setting disable directive Disable the SW0018 setting. 1 1: If SB0018 is disabled (OFF), the system switching monitoring time is 2s (default). POINT The network module issues the system switching request to the QnPRHCPU even when the data link error is caused by the following accident: the network module mounted in the control system is not connected with a cable or disconnected at the time of power ON. The network module issues the system switching request within 4s after power ON. 7 - 40 7 - 40