REPLACEMENT OF CC-LINK
8.5 Parameter Comparisons
(1) A/AnS series
: Compatible,
Specifications
Parameter name
AJ61BT11/A1SJ61BT11
: Partial change required, × : Incompatiblee
CompatQJ61BT11N
ibility
Precautions for
replacement
Newly set the parameter
Network parameter
Set this parameter with the
Set this parameter with GX
sequence program (TO
Developer or with dedicated
instruction) or with dedicated
instruction (RLPASET
instruction (RLPA instruction).
instruction).
with GX Developer or the
dedicated instruction
(RLPASET instruction).*1 *2
Specify [Remote net Ver.1
mode] or [Remote I/O net
mode] for the mode.
Perform the automatic
refresh setting with GX
Developer or read/write
Read/write cyclic data with
Perform the automatic refresh
Automatic refresh
FROM/TO instruction or set
setting with GX Developer or
parameter
this parameter with dedicated
read/write cyclic data with
cyclic data with FROM/TO
instruction.
When setting the network
parameter with dedicated
instruction (RRPA instruction). FROM/TO instruction.
instruction (RLPASET
instruction), read/write
cyclic data with FROM/TO
instruction.
(2) QnA/QnAS series
: Compatible,
Parameter name
Specifications
AJ61QBT11/A1SJ61QBT11
: Partial change required, × : Incompatible
CompatQJ61BT11N
ibility
Precautions for
replacement
Newly set the parameter
with GX Developer or the
dedicated instruction
Set this parameter with GX
Network parameter
Developer or sequence
program (TO instruction).
Set this parameter with GX
(RLPASET instruction).*1 *2
Developer or with dedicated
Up to 4 modules can be set
instruction (RLPASET
when setting with GX
instruction).
Developer.
Specify [Remote net Ver.1
mode] or [Remote I/O net
mode] for the mode.
Set the automatic refresh
with GX Developer or read/
write cyclic data with
Perform the automatic refresh Perform the automatic refresh
FROM/TO instruction.
Automatic refresh
setting with GX Developer or
setting with GX Developer or
When setting the network
parameter
read/write cyclic data with
read/write cyclic data with
parameter with dedicated
FROM/TO instruction.
FROM/TO instruction.
instruction (RLPASET
instruction), read/write
cyclic data with FROM/TO
instruction.
*1
Parameter setting of Q series CC-Link modules
Parameters can be set on up to eight modules using GX Developer. For the settings of the 9th module or later, use the
dedicated instruction.
For details, refer to the CC-Link System Master/Local Module User's Manual.
*2
Delete the program for the network parameter setting of the existing module.
8 - 11