WEEP CYCLE CHART
AT 120 SECOND CYCLE @ 40° START TEMP
(= DIP SWITCH 1 ON, 2 ON, 3 ON)
ZONE 1
=
DIP SWITCH 4 OFF, 5 OFF
FLOW %
TEMPETURE RANGE
FLOW ON (SEC.)
10%
40° - 36°
12
30%
35° - 31°
36
50%
30° - 26°
60
70%
25° - 21°
84
90%
20°
108
100%
19° AND UNDER
CONTINUOUS
FLOW OFF (SEC.)
108
84
60
36
12
0
ZONE 2
=
DIP SWITCH 4 OFF, 5 ON
FLOW %
TEMPETURE RANGE
FLOW ON (SEC.)
20%
40° - 36°
24
40%
35° - 31°
48
60%
30° - 26°
72
80%
25° - 21°
96
100%
20°
CONTINUOUS
100%
19° AND UNDER
CONTINUOUS
FLOW OFF (SEC.)
96
72
48
24
0
0
ZONE 3
=
DIP SWITCH 4 ON, 5 OFF
FLOW %
TEMPETURE RANGE
FLOW ON (SEC.)
30%
40° - 36°
36
50%
35° - 31°
60
70%
30° - 26°
84
90%
25° - 21°
108
100%
20°
CONTINUOUS
100%
19° AND UNDER
CONTINUOUS
FLOW OFF (SEC.)
84
60
36
12
0
0
ZONE 4
=
DIP SWITCH 4 ON, 5 ON
FLOW %
TEMPETURE RANGE
FLOW ON (SEC.)
100%
40° - 36°
CONTINUOUS
100%
35° - 31°
CONTINUOUS
100%
30° - 26°
CONTINUOUS
100%
25° - 21°
CONTINUOUS
100%
20°
CONTINUOUS
100%
19° AND UNDER
CONTINUOUS
13
FLOW OFF (SEC.)
0
0
0
0
0
0