Download 5 - Advanced Test Equipment Rentals
Transcript
DC HiPot Testing − The DC HiPot test component of the tester can test the insulation between any two conductors. For example, it may be used to test the insulation between feeder cables and the ground lead on the others. Follow the same procedures outlined for HiPot Testing. Change these connections to test all cables. Resistance temperature compensation When HiPot testing, temperature and humidity will have an influence which, can distort the results. It is also important to ensure that the test pieces insulation is dry and clean. The Rule of Thumb for determining the effect of temperature on resistance measurements is that resistance halves for each 10oC (Celsius) rise in winding temperature. Usually, the baseline temperature is 40oC for windings. This rating is usually found on the motors data plate. The following two examples illustrate this relationship. Example 1: If a resistance measurement of 100 mega-ohms is taken at 30oC, the resistance should be 50 mega-ohms at 40oC (an increase of 10oC). Example 2: If a resistance measurement of 200 mega-ohms is taken at 50oC, the resistance should be 400 mega-ohms at 40oC (a decrease of 10oC). 12/2/2009 | 71-002-V5 EN ST103A, ST106A, ST112A 25