Overview of Alarms
01/2008
NCK alarms
Remedy:
Enter a skip level (number behind the slash) less than 8.
Program Continuation:
Clear alarm with NC START or RESET key and continue the program.
14070
Channel %1 block %2 memory for variables not sufficient for subroutine
call
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
A called subroutine cannot be processed (opened), either because the internal data memory to be created for general purposes is not large enough, or because the available memory for the local program
variables is too small. The alarm can only occur in MDI mode.
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Analyze the part program section:
1. Has the most useful data type always been selected in the variable definitions? (For example REAL
for data bits is poor; BOOL would be better)
2. Can local variables be replaced by global variables?
Program Continuation:
Clear alarm with the RESET key. Restart part program
14080
Channel %1 block %2 jump destination %3 not found
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = Jump destination
Definitions:
In conditional and unconditional jumps, the jump destination within the program must be a block with
a label (symbolic name instead of block number). If no jump destination has been found with the given
label when searching in the programmed direction, an alarm is output.
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Check NC part program for the following possible errors:
1. Check whether the target designation is identical with the label.
2. Is the jump direction correct?
3. Has the label been terminated with a colon?
Program Continuation:
Clear alarm with NC START or RESET key and continue the program.
14082
Channel %1 block %2 label %3 program section not found
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = Start or end label
Definitions:
The start point for repetition of the program part with CALL <program name> BLOCK <start label> TO
<end label> has not been found or the same program part repetition has been called recursively.
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Check the start and end labels for programming repetition in the user program.
Program Continuation:
Clear alarm with NC START or RESET key and continue the program.
14085
Parameters:
2-174
Channel %1 block %2 instruction not allowed
%1 = Channel number
%2 = Block number, label
© Siemens AG, 2008. All Rights Reserved
SINUMERIK 840D sl, 840Di sl, SINAMICS, Diagnostics Manual (DAsl), 01/2008