Menu 2, Screen 2 – Water Temps and Flows 2. Water Temps/Flow hh:mm mon-dd-yy (*) PulldwnRate= X.X° /M Evap Flow= XXXgpm Ent Ht Rcvy=N/A °F Cond Flow= XXXgpm Lvg Ht Rcvy=N/A °F Menu 3, Screen 2 – Refrigerant Temps/Press 3.Refrig Temps/Press hh:mm mon-dd-yy Lift Press= XX.Xpsi Lift Temp= XX.XºF (*) Calc Lift Speed= XXX% Menu 9, Screen 1 – Network Status 9. Network Status hh:mm mon-dd-yy Master Command=Auto Compress Req. One Slave Command=Stop Status=Lead&Lag Off Lead Unit=Slave (*) LagShtdwnDT = XX°F Menu 11, Screen 1 – Control Mode 11.Control Mode hh:mm mon-dd-yy Mode= Manual Off (etc) (*) MinVFDSpeedSpt =XXX% (*) Max Speed Spt =XXX% Menu 11, Screen 2 – Control Mode Setpoints 11.Control Mode hh:mm mon-dd-yy Sample Time =XXSec Max Spd Step = XX% Mod Limit = X.XºF Lock VFD Speed Off (On) Deadband = X.XºF This entire screen only appears when a VFD is used Lock Speed @ XXX% Menu 13, Screen 1 – Motor Amp Setpoints 13. Motor Amp Spts hh:mm mon-dd-yy Amp Reset=No Reset Active Spt =XXX% Reset Signal=XX.Xma (*) Min Amp Spt =XXX% Network Spt =XXXA (*) Max Amp Spt =XXX% Menu 13, Screen 2 – Motor Amp Setpoints 13. Motor Amp Spts hh:mm mon-dd-yy Soft Load =Off (*) Dual Speed Spt = XXX% Begin Amp Lim= XX% (*)LagPDRateSpt = X.X°/M Ramp Time= XXMin Menu 23, Screen 1 – Dual / Network Setpoints 23. Dual / Net Spts 42 hh:mm mon-dd-yy Slave Address=01.01 Start-up=Unload LL Mode=Auto (*)LagStrtup DT=X.X°F LL SwOver=N/A 00:00 (*) LagShtdnOffst= X.X° IOMM 1159