Mobile Wireless
15.1 Basic principles
WLAN area
A WLAN area is the area of wireless coverage of the network with a sufficient signal strength
to allow the HMI device to communicate with the PLC. A Mobile Panel Wireless is used for
operator control and monitoring of the plant in a WLAN area.
Zone
A zone (1) is a spatial area immediately upstream of a machine or plant (4) registered by the
Mobile Panel (5). This allows the HMI device to respond specifically when the zone is
entered. For example, you can set it up so that the screen changes to the correct process
display.
In a hard-wired Mobile Panel, the length of the connecting cable defines a zone around a
connection box. With a Mobile Panel Wireless, the distance from one or more transponders
(3) on the machine defines a zone within the WLAN area.
Effective range
Safety-related operator input is only possible in a limited part of a WLAN area upstream of a
machine or plant (4). This is known as the effective range (2). One exception to this rule is
the emergency stop, which works in the entire WLAN area. For all other safety-related
operator input, the following requirements must be fulfilled:
● The HMI device (5) supports fail-safe operation, e.g. Mobile Panel 277F IWLAN.
● The HMI device is incorporated into the PROFIsafe communication.
● The HMI device must be logged into the effective range.
The HMI device can only log in within the effective range. This also requires there to be no
other HMI device logged into the same effective range.
The concept of the effective range ensures the necessary spatial assignment of the Mobile
Panel to the machine, reliably and with no wireless obstacles. This increases the reliability,
fail safety and access control to create a holistic safety concept within the effective range.