PROFIBUS–DP Connection to SIMATIC 505
12.2
Configuring SIMATIC 505 for PROFIBUS–DP
Parameter
When defining a new project, the project assistant requests the specification
of a PLC. First of all, select the protocol SIMATIC 500/505 DP V5.1
and then define the following parameters after clicking on the button Parameter. For any subsequent parameter modifications, select the item PLC in the
project window.
Define the following parameters for the PLC:
Table 12-1
PLC parameters
Parameter
Explanation
OP address
PROFIBUS–DP address of the operating unit.
Value range 3 to 126
Interface
Select the interface on the operating unit via which connection to the
PLC is to be established. When using a PC, this is DP/MPI, and
with the OP37/Pro and MP270, IF1B.
In the case of the OP37/Pro, ASPC2 must also be activated in the
BIOS. In the mask Integrated Peripherals, set the OP37/Pro BIOS
entry ASPC2 to Enabled.
Baud rate
The baud rate at which communication takes place over the network.
The baud rate must be set identically for all the units in the network.
The following baud rates are possible:
– 93.75 kBit/s
– 187.5 kBit/s
– 500 kBit/s
– 1.5 MBit/s (default)
– 12 MBit/s
Set
configuration
Used to define the I/O area implemented for the communication area
between the operating unit and PLC. The size of the I/O area influences the performance.
The set configuration must be realized according to Class B (basic
DP slave complying to EN 50170). There are four different set configurations from which to choose:
– Class B tiny
– Class B small
– Class B middle
– Class B big
Table 12-2 indicates the assignment of the I/O area.
The settings in ProTool/Pro must correspond to configuration specifications
of the connection module CP5434–DP.
Set configuration
The assignment of the I/O area is explicitly defined with the four different
settings. Table 12-2 provides details of the I/O area assignment.
Communication for Windows-based Systems User’s Manual
Release 01/99
12-5