C-0-2013 SERCOS I-O Configuration List
Attributes:
Variable-length list, read only
The CLC handles SERCOS I-O from DDS drives and SERCOS I-O stations.
DDS drive I-O is configured in axis parameters A-0-0011 Drive I/O Card 1
Setup, A-0-0014 Drive I/O Card 2 Setup, and A-0-0017 Drive I/O Card 3
Setup. SERCOS I-O stations such as Lutze DIOFACE are automatically
configured, and no parameters need to be set (see SERCOS I-O and Lutze
documentation).
Each step of this list presents the SERCOS I-O configuration in the following
format:
Register SERCOS_address Parameter_IDN Direction Number_of_registers
>CD 1.2013.3 100 11 2066 I 1
|
|
|
| |_number of registers (1, 2, 3, or 4)
|
|
|
|_’I’= input, ‘O’= output
|
|
|_SERCOS IDN (corresponds to card or module number)
|
|_SERCOS device address
|_Register number
Example:
> CD 1.2013.0 4 $E1
;4 elements in list
> CD 1.2013.1 40 1 32850 I 1
;drive 1 DEA 4.1 input at register 40, one register
> CD 1.2013.2 41 1 32849 O 1
;drive 1 DEA 4.1 output at register 41, one register
> CD 1.2013.3 100 11 2066 I 1
;I-O station 11 module 0, input register 100, one register
> CD 1.2013.4 102 11 2086 O 1
;I-O station 11 module 2, output register 102, one register
> CD 1.2013.5 !19 List is finished
;end of list
C-0-2014 Start of SERCOS I-O Station Registers
The CLC supports I-O stations that conform to the SERCOS I-O
specification, including the Lutze Dioface. CLC GPS-06 can support up to 8
SERCOS I-O stations. A variety of digital and analog I-O Modules can reside
on each I-O station.
C-0-2014 selects the starting register number for the group of registers that
are to be allocated to the SERCOS I-O Stations. If this parameter value is
non-zero, the CLC detects the I-O stations on the SERCOS ring and
automatically configures them based on the modules that are present. A
parameter list (C-0-0213) of configuration strings indicates the I-O modules
that were found and the registers that they are mapped to.
Addresses of I-O Slaves: On the Lutze Dioface, the SERCOS address of
an I-O station is selected with 8 binary switches located on the bottom of the
SERCOS module. The address can be set to any number that does not
conflict with any other drive or I-O station on the SERCOS ring. A list of I-O
stations found on the ring is provided in the CLC system parameters.
I-O Station Configuration: The configuration parameters for each I-O
module reside at the I-O station, and are communicated via the SERCOS
service channel. A parameter list for each module on the station is provided
through SERCOS. Refer to the Lutze DIOFACE Manual or SERCOS I-O
Specification. Digital I-O will usually work without additional
3-60
Parameters
DOK-VISMOT-VM*-06VRS**-FBK1-AE-P