Shanghai STEP Electric Corporation
Chapter 6
Functional Parameters
speed reference 0 input; if the function code is 4 (or 104), the related port is defined as digital
multi-section speed reference 1 input; if the function code is 5 (or 105), the related port is defined as
digital multi-section speed reference 2 input; if the function code is 6 (or 106), the related port is
defined as digital multi-section speed reference 3 input; Do they work only when P03.00 is set to 1
(digital multi-section speed reference). Combined these inputs and given the multi-section speed
reference command. Details refer to the explanation in Table 6.2.
3) When function code is 15 (or 115), the related port is defined as external encoder phase angle
adjusting command. Because the inverter has automatic encoder phase angle adjusting function, this
command is not required in normal situation. This function is only prepared for special user.
4) As to the function code 16 (or 116), the relates the port is defined as operation signal input in
emergency power supply. This function code is used to define input ports for emergency power
operation signal. The input port must be defined if there is an emergency operation function.
Corresponding to that input signal at the input ports, the elevator operates in emergency power
supply mode. The inverter allows to be operated in low speed by low bus cable voltage.
5) For thefunction code 7 (or 107), 8 (or 108), the corresponding port definition are upward
going signal and the downward going signal. This function code defines the input port for elevator
upward going signal and downward going signal. Upward going and downward going signals must
be available in all kinds of speed reference mode (digital multi-section speed reference, analog
voltage speed reference). Function code 7 (or 107), 8 (or 108) can only define one port respectively,
can’t define multi ports.
6) Function code 18 (or 118) relates the port for base block signal input. If there is base block
signal at input terminal, inverter will cut off the power module output right away.
7) Function code 19 (or 119), 20 (or 120) match to the input of light load switch and heavy load
switch. These two input ports must be defined if light load switch, heavy load switch simple torque
compensation method (P04.01 is 1) is used by system.
Note 2: Definition for some special function inputs at their factory default setting
1) Input port for controlling inverter operation signal
P05.06 = 7, X6 is defined as input port for up going command signal
P05.07 = 8, X7 is defined as input port for down going command signal
P05.05 = 18, X5 is defined as input port for base block
2) Input port for multi-section speed reference command
P05.00 = 3, X0 is defined as input port for multi-section speed reference 0
P05.01 = 4, X1 is defined as input port for multi-section speed reference 1
P05.02 = 5, X2 is defined as input port for multi-section speed reference 2
In elevator control system, most elevator speed doesn’t exceed 2.5 m/s. Three multi-section
speed references input port (can be combined to 7 speed reference commands) are enough in this
case. The default factory setting defines only three speed reference input ports. If elevator speed
exceeds 3 m/s and using digital multi-section speed reference mode, function code 6 (or 106) must
also be defined as multi-section speed reference 3 for input port.
Note 3: Input contact NO, NC setting
In order to use digital input port simply, all contacts of input ports can be set as NO or NC as
user wishes. NO means the input signal is valid if it is connected among the input signal and XC
62