Description of the Function Blocks Setting the Sampling Time The sampling time should not be higher than 10% of the calculated reset time. You can set the sampling time with the CYCLE parameter of FB TUNING_S and of the controller. It must match the time difference between two FB TUNING_S calls (cycle time of the cyclic interrupt OB, taking into account the counter settings). Complete Restart If the TUN_ON input has the value TRUE or if no initial tuning has been run during a complete restart, an initial tuning of the step controller is performed in the subsequent cycles. The PHASE output is set to 1. If the TUN_ON input has the value FALSE and if initial tuning has already been performed, the step controller continues to use its old parameters in the subsequent cycles. The PHASE output is set to 4. 2-22 PID Self-Tuner C79000-G7076-C825-01