Download Solar compact controller
Transcript
Actual release takes place only if the electric immersion heater can operate according to setting "El imm heater optg mode" (5060). El immersion heater control External thermostat The DHW storage tank is charged with an external thermostat without setpoint compensation by the controller. DHW sensor The DHW storage tank is charged with an electric immersion heater, with setpoint compensation by the controller. To ensure that setpoint compensation operates as required, the external thermostat must be set to the minimum storage temperature. 6.9.7 DHW push Line no. Operating line 5070 Automatic push Off On. Automatic push The DHW push can be automatically triggered. With the DHW push, the DHW is heated up once until the nominal setpoint is reached. Off DHW push is switched off. On If the DHW temperature falls by more than 2 switching differentials (5024) below the reduced setpoint (1612), one-time charging to the nominal DHW setpoint (1610) will take place again. The solid fuel boiler or collectors conduct the automatic push if they supply sufficient energy. Otherwise, the electric immersion heater or an external generator (via heat request K27) can be used. 6.9.8 With solar integration Plant hydraulics Line no. Operating line 5093 With solar integration Set whether the DHW storage tank receives its heat from the solar collectors. 6.9.9 Transfer Line no. Operating line 5130 Transfer strategy Always ¦ DHW release Transfer strategy Transfer is permitted either always or at the release times set (1620). 40 / 64 Siemens Building Technologies Solar compact controller The settings in detail CE1U2396en 18.08.2010