SLC File Reference
Example 2
In this example we want:
•
channel 1 enabled
•
Auto Address Programming enabled on channel 1
•
run-time parameter changes enabled on channel 1
•
configuration done via the serial port
To accomplish this:
1.
Write 13635 (=3543h) to word 63 in the G file.
2.
Write E000h (=1110 0000 0000 0000) to word 1 to enable the
channel, run-time parameter changes, and Auto Address
Programming on channel 1.
3.
Write 0 to word 2 to disable configuration from the G file.
Example 3
In this example, we want:
•
channel 1 enabled
•
Auto Address Programming enabled on channel 1
•
run-time parameter changes disabled on channel 1
•
SLC Faults disabled
We will use the G file for configuration on channel 1. The following slaves
will be configured:
Slave
Parameters
ID
I/O
1
F
0
7
2
F
0
3
3
F
0
0
5
F
0
8
7
9
1
1
To accomplish this, follow these steps:
1.
Write 13635 (=3543h) to word 63 in the G file.
43