Main Functions
1.3
SiBE12-713
Operation Starting Control
FTXG25-35E, CTXG50E
The system carries out the following control at the beginning to conduct every functional parts
properly.
1. Opening the front panel fully
2. Output of the ∆D signal after the front panel starts moving
3. Opening the flap fully after the front panel opens fully
4. Making the fan rotate when the flap passes over the fan-banned area
Control Flow
Start
Opening the front panel
fully
Opening the flap fully
Output of the ∆D signal after
the front panel starts moving
Making the fan rotate when
the flap passes over the
fan-banned area
Running
(R3311)
Timing Chart
Start
OFF
Operation
starting control
ON
Fully close
Front
panel
Fully open
Fully open
Flap
Fan-banned area
Under running control
Fully close
Right
Louvers
Under running control
Left
ON
Fan
Under operation mode control
OFF
Output
Under operation mode control
∆D
∆0
TDELTA
Force supply
(from the
outdoor unit)
ON
The outdoor unit provides force
when it receives the ∆D signal.
OFF
(R3312)
64
Function and Control