Go to sheet G No Check partial load setting Yes Replace electronic board Check operation of boiler in DHW mode, does flame increase in size to full rate? (TURBOmax Plus only) Check connections and modulator, replace gas valve if burner still fails to increase to full rate Yes (see page 53) equals 1 (TURBOmax Plus only) Check diagnostic code D.22 No No Yes Does burner flame modulate/ go out when radiator temperature control is turned left to the horizontal position at flow temperature of approx. 50 C? No Does flame indicator glow and flames increase in size to full gas rate after approx. 2 mins? No Yes Replace diverter valve Yes Does spindle move? Turn "ON" the main ON/OFF control Insert a small screwdriver through the hole in the front of the diverter valve and hold blade lightly against spindle Turn main ON/OFF control to the "0" position (TURBOmax Plus only) Yes Ensure flow and return service valves are open No Does heating flow pipe temperature rise? Check operation of burner and modulation No Yes Replace electronic board Go to sheet G Sheet F FAULT FINDING 83