Table 3—Wet Coil Air Delivery* — Horizontal Discharge
(Deduct 10% for 208--Volt Operation)
230 VOLT HORIZONTAL DISCHARGE
UNIT
SIZE
MOTOR
SPEED
Low
024
Med
High
Low
030
Med
50SD
High
Low
036
Med
High
Low
042
Med
High
Low
048
Med
High
Low
060
Med
High
AIR
DELIVERY
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
0.1
311
935
—
—
—
—
311
935
411
1195
—
—
437
1353
—
—
—
—
625
1539
—
—
—
—
627
1550
771
1798
—
—
786
2027
873
2095
1012
2184
0.2
309
885
—
—
—
—
309
885
405
1155
—
—
433
1318
—
—
—
—
606
1496
741
1738
—
—
617
1530
755
1771
—
—
769
1960
849
2026
993
2109
0.3
304
820
—
—
—
—
304
820
398
1100
—
—
424
1283
—
—
—
—
586
1466
715
1698
—
—
607
1493
734
1734
908
2000
754
1901
833
1962
981
2036
EXTERNAL STATIC PRESSURE (IN. WC)
0.4
0.5
0.6
0.7
301
286
—
—
757
686
—
—
—
379
357
357
—
957
868
769
—
—
—
447
—
—
—
970
301
—
—
—
757
—
—
—
390
379
357
357
1028
957
868
769
—
477
467
447
—
1185
1088
970
417
403
391
379
1235
1187
1123
1059
531
516
496
478
1489
1437
1362
1289
—
—
—
—
—
—
—
—
571
550
534
509
1437
1387
1330
1264
694
669
645
610
1653
1604
1538
1457
—
—
798
772
—
—
1720
1648
584
567
548
528
1461
1414
1361
1320
711
690
665
639
1687
1645
1595
1530
887
858
827
804
1994
1876
1811
1735
736
722
705
684
1821
1759
1693
1616
815
798
782
763
1887
1817
1748
1679
963
948
927
904
1963
1886
1812
1729
0.8
—
—
345
647
435
853
—
—
—
—
435
853
362
975
459
1208
629
1470
483
1183
573
1362
738
1540
503
1250
607
1449
767
1647
658
1513
748
1583
886
1647
0.9
—
—
327
365
421
712
—
—
—
—
—
—
—
—
435
1099
602
1357
457
1093
544
1271
700
1414
—
—
572
1355
748
1555
—
—
—
—
—
—
1.0
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
*Air delivery values are based on operating voltage of 230v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain
static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
12