Download Carrier 50SD Instruction manual
Transcript
Table 3—Wet Coil Air Delivery* — Horizontal Discharge (Deduct 10% for 208--Volt Operation) 230 VOLT HORIZONTAL DISCHARGE UNIT SIZE MOTOR SPEED Low 024 Med High Low 030 Med 50SD High Low 036 Med High Low 042 Med High Low 048 Med High Low 060 Med High AIR DELIVERY Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM 0.1 311 935 — — — — 311 935 411 1195 — — 437 1353 — — — — 625 1539 — — — — 627 1550 771 1798 — — 786 2027 873 2095 1012 2184 0.2 309 885 — — — — 309 885 405 1155 — — 433 1318 — — — — 606 1496 741 1738 — — 617 1530 755 1771 — — 769 1960 849 2026 993 2109 0.3 304 820 — — — — 304 820 398 1100 — — 424 1283 — — — — 586 1466 715 1698 — — 607 1493 734 1734 908 2000 754 1901 833 1962 981 2036 EXTERNAL STATIC PRESSURE (IN. WC) 0.4 0.5 0.6 0.7 301 286 — — 757 686 — — — 379 357 357 — 957 868 769 — — — 447 — — — 970 301 — — — 757 — — — 390 379 357 357 1028 957 868 769 — 477 467 447 — 1185 1088 970 417 403 391 379 1235 1187 1123 1059 531 516 496 478 1489 1437 1362 1289 — — — — — — — — 571 550 534 509 1437 1387 1330 1264 694 669 645 610 1653 1604 1538 1457 — — 798 772 — — 1720 1648 584 567 548 528 1461 1414 1361 1320 711 690 665 639 1687 1645 1595 1530 887 858 827 804 1994 1876 1811 1735 736 722 705 684 1821 1759 1693 1616 815 798 782 763 1887 1817 1748 1679 963 948 927 904 1963 1886 1812 1729 0.8 — — 345 647 435 853 — — — — 435 853 362 975 459 1208 629 1470 483 1183 573 1362 738 1540 503 1250 607 1449 767 1647 658 1513 748 1583 886 1647 0.9 — — 327 365 421 712 — — — — — — — — 435 1099 602 1357 457 1093 544 1271 700 1414 — — 572 1355 748 1555 — — — — — — 1.0 — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — *Air delivery values are based on operating voltage of 230v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain static pressure available for ducting. NOTES: 1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below this point. 2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended. 12