Download Viessmann Vitodens 300 Operating instructions
Transcript
Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Boiler control unit User no. 1 Code 77:1 Control unit is fault manager * 1 Code 79:1 Sent time via LON Code 7b:1 Transmit outside temperature via LON Set code 97:2 Fault monitoring LON user code 9C:20 Vitotronic 050 Vitotronic 050 Vitocom User no. 10 Code 77:10 Control unit is not fault manager * 1 Code 79:0 Time received via LON Set code 81:3 Outside temperature is received via LON Set code 97:1 Fault monitoring LON user code 9C:20 User no. 11 Set code 77:11 Control unit is not fault manager * 1 Code 79:0 Time received via LON Set code 81:3 Outside temperature is received via LON Set code 97:1 Fault monitoring LON user code 9C:20 User no. 99 Control unit is fault manager Time received via LON — — Implementing a user check (in conjunction with the LON system) *1 In 32 each heating system, only one Vitotronic may be encoded as fault manager. 5692 550 GB Communication with the system devices connected to the fault manager is tested with a user check. Preconditions: & The control unit must be encoded as fault manager (code 79:1). & The LON user number must be encoded in all control units (see page 31). & The fault manager user list must be up to date (see page 31).