Installation and Wiring: 2.9 Zone Wiring for the panel (section [013], options [1] and [2]). See 5.1 “Zone Definitions”. If you change the zone supervision options from DEOL to EOL or from NC to DEOL (section [013], options [1] or [2]), you should power down the system completely, and then power it back up. If you do not, the zones may not work correctly. Normally Closed (NC) Loops To enable normally closed loops, programming section [013], option [1] must be ON. NOTE: This option should only be selected if Normally Closed (NC) devices/contacts are being used. NOTE:If the Double EOL supervision option is enabled, all hardwire zones must be wired for Double EOL resistors, except for Fire and 24 Hour Supervisory zones. Do not wire DEOL resistors on keypad zones. Do not use DEOL resistors for Fire zones or 24 Hour Supervisory zones. Do not wire Fire zones to keypad zone terminals if the DEOL supervision option is selected. This option can only be selected if Normally Closed (NC) detection devices or contacts are being used. Only one NC contact can be connected to each zone. The following chart shows zone status under certain conditions: Loop Resistance Loop Status 0Ω (shorted wire, loop shorted) 5600Ω (contact closed) Infinite (broken wire, loop open) 11200Ω (contact open) Fault Secure Tamper Violated End-of-Line Resistors . . . . . . . . . . . . . .Section [013], Option [1] Double End-of-Line Resistors . . . . . . . .Section [013], Option [2] Normally Closed Loops. . . . . . . . . . . . Section [013], Option [1] Single End Of Line (EOL) Resistors To enable panel detection of single end-of-line resistors, programming section [013], options [1] and [2] must be OFF. Fire Zone Wiring - 4-wire Smoke Detectors All zones defined as Fire (see section 5.1 “Zone Definitions” on page 20) must be wired according to the following diagram: NOTE: This option should be selected if either Normally Closed (NC) or Normally Open (NO) detection devices or contacts are being used. For a complete description of how fire zones operate, see section 5.1 “Zone Definitions” on page 20. Keyswitch Zone Wiring Zones may be programmed to be used as keyswitch arming zones and must be wired according to the following diagram: End of Line Resistors . . . . . . . . . . . . . Section [013], Option [1] Single End of Line Resistors . . . . . . . . Section [013], Option [2] Double End of Line (DEOL) Resistors Double End of Line resistors allow the panel to determine if the zone is in alarm, tampered or faulted. To enable panel detection of double end of line resistors, programming section [013], option [1] must be OFF and option [2] must be ON. For a complete description of how keyswitch zones operate, see section 5.1 “Zone Definitions” on page 20. LINKS1000 Supervisory (24 Hour Supervisory) When using the LINKS1000 cellular communicator, any main board zone may be configured for LINKS1000 Supervision. Program this zone as zone type (09), 24 Hour Supervisory in section [001]. With a 24 Hour Supervisory zone, if the LINKS1000 experiences a trouble, the zone will be violated, causing the panel to report the event to the central station. This type of zone always requires a single EOL resistor (5600Ω). Wire this zone according to the diagram: 9