Mechanical
Electrical Hazard: Turn off the cooling unit and disconnect all power sources. Perform Lockout/
Tagout procedures before performing any electrical or mechanical service. Wear appropriate
personal protective equipment when checking hazardous voltages.
‰
Check the fans. All components should be moving freely with no signs of binding or damages.
‰
Verify that the condensate line is flowing freely.
Electrical
Electrical Hazard: Turn off the cooling unit and disconnect all power sources. Perform Lockout/
Tagout procedures before performing any electrical or mechanical service. Wear appropriate
personal protective equipment when checking hazardous voltages.
‰
Inspect the electrical panel for tight connections and overheated connections from loose contact terminals.
‰
Confirm the incoming main voltage matches the cooling unit nameplate. The measurement should be
within 10% of the nameplate listing.