Download Emerson 1410 Technical data
Transcript
System Installation 3.3.2.2 Power Cable Termination Custom lugs are used with large gauge wires for up to 80 AMPs DC (4 AWG) when connecting to the PEM. These are shipped with the product.The lugs are angled to allow the cables to be dressed below the cable management tray, thus protecting the circuit breakers from accidental tripping. Terminating this lug is identical to terminating standard lugs. To minimize shorting of the terminals, the lugs must be insulated according to the following illustration. Heat shrink should be placed as close to the hole as possible (0.15") apart. The heat shrink tube should be cut approximately at a 30° angle. 3.3.2.3 Connecting the Cables to the PEM In a redundant configuration, each PEM must be connected to a separate DC power source. Power is introduced to each PEM’s terminal block on the front of the module (power input cable and return cable). The lugs provide secure contact for the cable and prevent the power cables from rotating. A plastic housing covers the power feeds and returns and is attached with one screw. Refer to Figure 3-2 for detail. To cable a dual breaker DC system, read all cautions and warnings, properly ground the equipment by following the procedure in Grounding the System on page 56, and follow these steps. This procedure assumes that the PEMs are preinstalled in the shelf. 54 AXP 1410 Installation and Use (6806800H70D)